PostBy: Cold_Mainer On: Wed Nov 19, 2008 8:18 pm

I'm looking to size up a ups / back up power supply for my stove. Need to figure out the amp draw from all the electrics. Does anyone know what it is? Has anyone retrofitted a ups onto their stove yet? Searched the forums but didn't come up with anything. I'm sure this has been done by someone somewhere.

Steve
Cold_Mainer
 
Hot Air Coal Stoker Furnace: Pocono BV 90,000 BTU
Coal Size/Type: Rice

Re: UPS For Pocono BV

PostBy: Hunlock On: Wed Nov 19, 2008 8:24 pm

As per LL website:

Feeder Motor - .55amps
Combustion Fan - .58amps
Convection Fan - 1.86amps
Power Venter - 1.77 amps or 136 watts

Tim
Hunlock
 
Stove/Furnace Make: Leisure Line
Stove/Furnace Model: Hyfire II

Re: UPS For Pocono BV

PostBy: Cold_Mainer On: Wed Nov 19, 2008 8:30 pm

Thank you.

Shame on me for not checking the web site. Guess I'll check to see what the coal trol system draws on thier web site.
Cold_Mainer
 
Hot Air Coal Stoker Furnace: Pocono BV 90,000 BTU
Coal Size/Type: Rice

Visit Leisure Line Stove

Re: UPS For Pocono BV

PostBy: WNY On: Wed Nov 19, 2008 9:26 pm

Do a search on here for Back UP Power Supply, many of us have different setups, either UPS, Inverters, generators, etc....
Make sure you get a decent one with a Modified or FULL SINE wave output, if you get the cheap UPS, it may have a square wave output and could damage your motors/blowers, it will definitely make them hummm pretty loud too.

More info on inverters/batteries.
Inverter for Homemade Battery Backup
WNY
 
Hot Air Coal Stoker Stove: Keystoker 90K, Leisure Line Hyfire I
Coal Size/Type: Rice
Stove/Furnace Make: Keystoker, LL & CoalTrol
Stove/Furnace Model: 90K, Hyfire I, VF3000 Soon