i have a Harman 360 boiler burning nut coal once the damper control shuts it down it never brings back the boiler up to temp again what am I doin wrong


 
User avatar
LsFarm
Member
Posts: 7383
Joined: Sun. Nov. 20, 2005 8:02 pm
Location: Michigan
Stoker Coal Boiler: Axeman Anderson 260
Hand Fed Coal Boiler: Self-built 'Big Bertha' SS Boiler
Baseburners & Antiques: Keystone 11, Art Garland

Post by LsFarm » Thu. Nov. 27, 2008 11:12 pm

How tall is your chimney?? Do you know how strong your draft is??? if you have marginal draft, it will be strong enough when a hot fire is in the boiler and the flue temps are high, but when the damper shuts down the fire when the aquastat is satisfied, the fire will die down, the flue temps will drop and it may not recover when the combustion damper opens again, because the flue is too cool.

Do you have any over the fire air vents open in the loading door?? you want them closed, these steal draft from the fire..

Hope this helps..