I have my boiler located in a seperate building about 130 feet from the house which it is heating. I would like to wire a low voltage alarm in the house when the Efm boiler drops below the low set point of the aquastat so that I know when I have a problem with the boiler.
Does anyone have any ideas that might help?
Low Temp. Alarm
- WNY
- Member
- Posts: 6307
- Joined: Mon. Nov. 14, 2005 8:40 am
- Location: Cuba, NY
- Hot Air Coal Stoker Stove: Keystoker 90K, Leisure Line Hyfire I
- Coal Size/Type: Rice
- Contact:
here one I found, but there are others.
Last edited by WNY on Sat. Apr. 01, 2017 1:35 am, edited 2 times in total.
Reason: <removed dead link>
Reason: <removed dead link>
Here's the one I use: http://www.smarthome.com/3219/Redi-Chek-ET-73-Rem ... ter/p.aspx
-
- New Member
- Posts: 18
- Joined: Wed. Jul. 16, 2008 8:29 pm
- Location: Lewisburg, Pa.
Thanks for the tips!
Devil, sounds like that would be a great alarm but it's only rated at 100 ft.
I was thinking of using a aquastat that would close the alarm circuit when the temp dropped below the set point. Install a wire from the aquastat to a septic tank alarm inside the house. Or maybe tie the aquastat into a seperate door bell chime. Just thinking???
Devil, sounds like that would be a great alarm but it's only rated at 100 ft.
I was thinking of using a aquastat that would close the alarm circuit when the temp dropped below the set point. Install a wire from the aquastat to a septic tank alarm inside the house. Or maybe tie the aquastat into a seperate door bell chime. Just thinking???
You're right. From the sound of it the low voltage alarm idea you have would work better & I'm sure someone must make such a wired unit so you don't have to jury rig something.heaterman87 wrote:Devil, sounds like that would be a great alarm but it's only rated at 100 ft.