Is there anyway to make one zone at a time go on rather than the whole house which brings the boiler temp down to a point where it doesn't heat effectively? I have the Taco SR506 Zone Switch.
Thanks,
Dave
Rob R. wrote:Why do all the zones call at once?
Rob R. wrote:Why do all the zones call at once?
lsayre wrote:I've been watching closely and with the colder weather I'm not seeing my boiler drop below 160 degrees, no mater how many zones are calling for heat, or in what sequence, including all at once. The phenomenon of having multiple simultaneously calling zones bring down the boilers temperature too much seems to be more likely with a "sleepy" boiler in warmer weather conditions than with a repeatedly revved up boiler in cold weather.
Sting, did it just take me about a hundred words to say what you had earlier said quite effectively in only about 15 words?