WL110 Not Keeping up

 
jeff216410
Member
Posts: 64
Joined: Wed. Oct. 20, 2010 11:51 am

Post by jeff216410 » Wed. Feb. 25, 2015 11:51 am

I'm currently running my 110 boiler with 6 zones of baseboard. My main house is 1 zone of Iron feed and return loop with iron baseboards that I always had problem heating. There is over 25 gallons of water in that zone alone along with 200 feet of 1 inch iron pipe and fittings. Add to that the thermal mass of the baseboard. I recently took 2 bedrooms off that zone and fed them with 3/4 pex which reduced the water volume by more than half. I have a ball valve on each zone and they are all barely 1/3 open. My boiler spends more time heating the zone instead of heating a few hundred pounds of iron pipe and water in the pumbing. LL is set at 180 and off at 165 and undershoots to about 155. If it undershoots below that I close the valve on that zone a little bit to restrict the flow more.


 
User avatar
Sting
Member
Posts: 2983
Joined: Mon. Feb. 25, 2008 4:24 pm
Location: Lower Fox Valley = Wisconsin
Other Heating: OBSO Lennox Pulse "Air Scorcher" burning NG

Post by Sting » Wed. Feb. 25, 2015 3:47 pm

KLook wrote:Slow the flow down. Got ta channel Sting here. System balance and all that.
Kevin
System Balancing ???

Whats that :D

see last post here
Rethinking Delta-T & Delta-P Circulator in Zone Valve System